This technical guide introduces seismic isolation, the modelling of isolators in midas Gen, and the boundary nonlinear time history analysis used to assess an isolated structure. It explains the dynamics that make isolation effective, the properties an isolation system must provide, the isolator types available in the software and their mathematical models, and then demonstrates the whole approach on a building analysed with and without isolators at its base. A section on the Indian context motivates the material with the Gujarat earthquake and the first base-isolated building in the country.
Key Topics
What Seismic Isolation Does
Isolation decouples a structure from damaging support motion by increasing the flexibility of the system while providing appropriate damping, most often as a base isolation layer beneath the structure. The lead rubber bearing is the most common technology, with dampers and sliders also in use, and installation cost is stated as a few percent of total construction cost. Beyond earthquakes, isolation is applied to control vibration from wind, moving loads and plant equipment, and in facilities such as semiconductor plants, computer centres and clean rooms.
The Dynamics of Isolation
Placing material of low horizontal stiffness between the structure and its foundation lengthens the vibration period relative to a fixed base, so the first mode consists almost entirely of isolator deformation with the superstructure moving as a rigid body and structural deformation confined to higher modes that do not dominate the response. Because the longer period falls in a lower-acceleration region of the response spectrum, the base shear is reduced. The counterpart is large deformation at the isolation level, which risks collision with adjacent structures, damage to piping and buckling of equipment, so a displacement limit is required; a higher displacement capacity gives greater energy dissipation, and the limit itself is obtained from the spectral displacement reduced for the effective damping.
Required Properties of an Isolation System
Three basic properties are required: flexibility that lengthens the structural period under load, the ability to dissipate energy so that displacement is reduced, and sufficient stiffness under wind load, ambient vibration and small loads so that the structure is not unnecessarily mobile. Additional considerations for the hardware include temperature-induced deformation, restoring capability and maintenance cost.
Isolators in MIDAS Software and the General Link
Both lead rubber bearings and friction pendulum bearings are covered, with their mathematical models set out; bearing sizes in practice range from roughly a metre in diameter to the very large bearings used on major bridges. Isolators and dampers are modelled with the General Link element, which behaves as a spring with six degrees of freedom connecting two nodes, with an effective stiffness definable for each degree of freedom and nonlinear properties definable either independently per degree of freedom or interactively. The same element can represent visco-elastic dampers, hysteretic systems, compression-only gaps and tension-only hooks.
Boundary Nonlinear Time History Analysis
When the isolators are nonlinear while the rest of the structure remains linear elastic, the problem is treated as nonlinear boundary analysis, and the member stresses must afterwards be verified to lie within the elastic range. The solution treats the structure in two parts, applying the member forces from the nonlinear elements as external dynamic loads within a modal time history analysis of the linear structure, with the Runge-Kutta-Fehlberg scheme used for the iterative integration. Linear response spectrum analysis with equivalent stiffness and equivalent damping satisfies the nonlinearity requirement in ordinary cases, but for strongly nonlinear isolators the code requires nonlinear time history analysis.
Analysis Conditions to Be Set
Running the nonlinear time history analysis requires choices of analysis method, load condition and load continuation, damping representation among modal, Rayleigh and energy proportional damping, the numerical integration scheme, and the nonlinear convergence criteria. Because superposition does not hold in a nonlinear analysis, static and dynamic seismic load results cannot simply be added; instead the static seismic load is scaled by a time function so the gravity load is applied first and the earthquake superimposed afterwards within the same analysis. This matters particularly for friction pendulum bearings, whose friction force is proportional to the axial load.
Worked Comparison Against a Fixed Base
The exercise building is a frame with gravity and wind loading, isolated with lead rubber bearings at the four corner columns and friction pendulum bearings at the remaining column bases, subjected to the two horizontal components of the El Centro record. Story drift, column shear force and isolator hysteresis are compared against the fixed base model. The results show the drift of the upper stories reduced, while the apparent top-story displacement increases because the isolator displacement adds to a superstructure that now moves as a rigid body; column shear forces are markedly reduced, and the isolator hysteresis loops confirm the energy dissipation, with the lead rubber loops distorted by the bidirectional shear interaction of the bilinear model while the friction pendulum loops behave similarly under the rigid diaphragm constraint.
Seismic isolation works by lengthening the structural period so that spectral acceleration and hence base shear fall, at the price of large displacement at the isolation level that must be limited and dissipated. midas Gen models lead rubber and friction pendulum bearings with the General Link element and solves the isolated structure by boundary nonlinear time history analysis, and the worked comparison confirms reduced story drift and column shear relative to a fixed base, with the isolator hysteresis showing where the energy is absorbed.