This note is the two-way counterpart of the gable hip roof wind load example, treating a roof that slopes in both plan directions with a different pitch in each. It works the ASCE 7-16 velocity pressure and pressure coefficient calculation by hand, produces the net pressures for both internal pressure cases and both wind directions, and then shows how to enter them in midas Gen as floor loads. The two-way geometry matters because the roof pressure coefficients must be selected separately for each slope.
Key Topics
Example Model with Two Roof Angles
The building has a mean roof height of about eight and a half metres and modest plan dimensions, with a roof pitch of roughly twenty-three degrees in one plan direction and twenty-six degrees in the other. It is assigned a basic wind speed of thirty metres per second, risk category two with unit importance factor, and exposure category C. Because each slope has its own angle, the windward roof pressure coefficient must be evaluated twice.
Velocity Pressure Factors
The velocity pressure combines the velocity pressure exposure coefficient, the topographic factor, the wind directionality factor, the ground elevation factor and the square of the basic wind speed. The elevation factor is unity and the directionality factor takes the standard building value. The exposure coefficient is interpolated from the code table at the mean roof height for the assigned exposure category.
Topographic Factor
The topographic factor is computed from three coefficients determined by the hill type, the height-to-length ratio of the feature, the distance from the crest and the height above ground, here for an assumed two-dimensional escarpment. Values are interpolated on the ratio of height to hill length. Because the height-dependent coefficient decays upward, the factor is largest at grade and smallest at the roof.
Velocity Pressure Distribution
Velocity pressure is tabulated at each level from ground to the mean roof height, combining the height-varying exposure and topographic factors, and reaches its maximum at the roof. The note adopts that maximum as a single value used throughout the pressure calculation, while noting that level-by-level values may be applied if desired. This keeps the subsequent hand calculation manageable.
Two Internal Pressure Cases
Net pressure is the external pressure minus the internal pressure, and since the internal pressure coefficient may be positive or negative, each surface has two candidate values. The calculation is therefore carried out twice, once with positive and once with negative internal pressure. Different surfaces govern in the two cases, so both must be modelled.
Pressure Coefficients for the Two Directions
With the gust effect factor at the standard assumed value, wall pressure coefficients for the windward, leeward and side walls are selected from the plan aspect ratio, which differs between the two wind directions because the plan is rectangular. Roof pressure coefficients are then selected for each slope from its own pitch together with the ratio of roof height to the relevant plan dimension. Each surface pressure follows as the velocity pressure times the gust factor times the coefficient.
Entering the Loads in midas Gen
Load cases are created to span the two internal pressure cases, the two plan wind directions and the two pressure signs, with separate entries for the windward, leeward and side surfaces. The computed pressures are entered as floor loads on the corresponding faces, with the sign corrected for the direction in which each load acts and a mirrored floor load type created for the opposite direction. Load combinations including the wind load cases complete the workflow.
For a hip roof that slopes in both plan directions, ASCE 7-16 wind pressures have to be derived by hand with the roof coefficients selected separately for each pitch and the wall coefficients selected for each plan aspect ratio, in both the positive and negative internal pressure cases. The resulting pressures are then entered in midas Gen as floor loads across a systematic set of load cases spanning case, direction and sign, and combined for design.