[EN_GEN] Pushover & TH_S04 TH Tutorial for evaluation of floor vibration

PDF
·
15ページ
·
2.0MB
·
English
·
2025.03.11 更新
概要

The fourth part of the midas Gen time-history series is a tutorial on evaluating vibration induced by rotating equipment in a plant structure. Although the series index labels this part as floor vibration, the worked example is a factory frame supporting a machine on rubber pads. It covers modeling the equipment mounting, converting loads to mass, deriving a harmonic dynamic load from the machine frequency, running a modal time-history analysis and comparing the response with DIN and ISO vibration limits.

主要内容

01

Model and Problem Setting

The structure is a factory frame whose slab supports vibrating equipment, and the study distinguishes the location where the dynamic load is applied from the locations where vibration must be assessed. Both the support points under the machine and the working positions on the floor are of interest. This separation of source and receiver defines what has to be extracted from the analysis.

02

Modeling the Equipment Mounting

The machine sits on rubber pads of stated height and spring stiffness, which are modeled as springs between the equipment and the supporting structure. The column bases are given their own boundary condition. Representing the isolation pads correctly is essential, since they control how much of the machine force reaches the structure.

03

Loading and Mass Conversion

Gravity load consists of self-weight plus a modest superimposed dead load, with the live load including the weight of the equipment itself, a load of several tonnes. Loads are converted into mass with the conversion restricted to the vertical direction for a floor vibration study. The equipment mass participates in the modes that the harmonic force will excite.

04

Deriving the Harmonic Dynamic Load

The machine operates at a known frequency, from which the circular frequency and the corresponding sinusoidal acceleration history are formed. Multiplying that acceleration by the machine weight and dividing by gravity gives the dynamic force history in force units, which is entered as a time function. The resulting function is a smooth sinusoid whose amplitude is a fraction of the machine weight, and it is pasted into the program as tabulated force data.

05

Setting the Time-History Load Case

The load case is defined with a linear modal analysis type, an end time and time increment consistent with the machine period, and modal damping with a conventional damping ratio for concrete. Linear modal analysis is appropriate here because the structure is expected to remain elastic under machine excitation. The settings are simpler than for a seismic inelastic run.

06

Extracting Velocity and Acceleration Histories

Graph functions are defined for velocity and acceleration in the vertical direction, referenced to the ground, and plotted against time for the target nodes. Velocity is needed for the structural stability assessment and acceleration for the human comfort assessment. The peak values and the frequency at which they occur are read from the graphs, and the response frequency matches the machine operating frequency as expected.

07

Assessment against DIN 4150-3

The peak velocity from the analysis is compared with the DIN 4150-3 allowable velocity for the relevant building category. In the example the computed velocity falls below the residential limit, so the structural stability requirement is satisfied. A separate continuous-vibration velocity threshold is noted, above which the stability of the structure itself becomes a concern.

08

Assessment against ISO Acceleration Criteria

Allowable root-mean-square accelerations are tabulated by room type, from quiet areas such as hospital operating rooms through residences with separate day and night values, to offices and factories, and separately for continuous and impulsive vibration. The computed peak acceleration is compared with the factory limit and exceeds it, so the structure does not satisfy the serviceability requirement and needs strengthening. The two-criterion outcome shows that a structure can be stable yet unserviceable.

まとめ

The tutorial demonstrates a complete machine-vibration assessment in midas Gen: model the equipment on its isolation springs, convert loads including the equipment weight to vertical mass, derive a sinusoidal force history from the machine frequency, and run a linear modal time-history analysis. Peak velocity is checked against DIN 4150-3 for structural stability and peak acceleration against ISO room-type criteria for serviceability, and in this example the structure passes the former but fails the latter and requires strengthening.