[EN_GEN] Analysis and Design of Structures using the Nodal Body Force Function

PDF
·
11ページ
·
453.2KB
·
English
·
2025.03.12 更新
概要

Some structures cannot be described with clear stories or floor diaphragms, so static seismic or wind loads cannot be applied in the usual way. This note explains how the Nodal Body Force function in midas Gen applies an equivalent static seismic load in such cases and compares the results with a conventional floor-diaphragm model.

主要内容

01

The Nodal Body Force Function

The function defines masses as loads in any direction. The base shear is computed per IS 1893:2002 from the seismic weight and the design horizontal seismic coefficient Ah, which depends on the zone factor Z, importance factor I, response reduction factor R and average response acceleration Sa/g. Ah is entered as the Nodal Body Force Factor and the mass is taken automatically from Nodal Mass, Load to Mass or Structure Mass.

02

Case 1 - Slab that is Not a Floor Diaphragm

For a slab that cannot be defined as a floor diaphragm, the design horizontal seismic coefficient is obtained from the Seismic Load Calc. Sheet and entered directly as the Nodal Body Force Factor for the corresponding direction.

03

Case 2 - Steel Structure with No Slabs

For an eight-story steel braced frame with no slabs, the nodes are selected and the design horizontal seismic coefficient is applied via the function. The resulting reactions match those of a model in which slabs are defined with floor diaphragms.

04

Case 3 - Story with Two Floor Diaphragms

For a ten-story RC structure whose second and third stories each split into two diaphragms connected by rigid links, the story seismic loads V2 and V3 are applied to the master nodes with per-story Nodal Body Force Factors Ah2 and Ah3 = Vb / (m*g); reactions again match the single-diaphragm model.

05

Comparison of Distribution Methods

For the steel structure, distributing the base shear by nodal mass gives larger story loads at lower stories, while code-based distribution gives larger loads at upper stories because of the height distribution coefficient k that accounts for higher modes. Maximum lateral displacement and member bending moments are larger when slabs are not defined with floor diaphragms.

まとめ

The Nodal Body Force function lets an equivalent static seismic load be applied to structures that lack usable floor diaphragms by distributing the base shear to nodal masses, giving results consistent with diaphragm-based models; the engineer must still choose the appropriate distribution method for each structure type.