[EN_GEN] Input a wind load in the model with gable hip roof as per ASCE 7-16

PDF
·
22페이지
·
2.2MB
·
English
·
2025.03.12 업데이트
요약

This note works through the manual calculation of ASCE 7-16 wind pressures for a building with a gable hip roof and then shows how to enter those pressures into a midas Gen model as floor loads. It follows the velocity pressure calculation factor by factor, derives the external and internal pressure coefficients for walls and roof surfaces, tabulates the resulting net pressures for both internal pressure cases, and finishes with the load case, load input and load combination steps in the program. The approach is needed because the roof geometry is not covered by the program's automatic wind load generation.

핵심 내용

01

Example Model Definition

The example is a low building of moderate plan dimensions with a mean roof height under ten metres and a single roof angle of about seventeen degrees, assigned a basic wind speed of thirty metres per second, risk category two with unit importance factor, and exposure category C. The plan dimensions in the two directions differ, which matters because the wall pressure coefficients depend on the ratio of the along-wind to the across-wind dimension. These parameters fix every factor in the subsequent calculation.

02

Velocity Pressure Factors

The velocity pressure is built from the standard coefficient times the velocity pressure exposure coefficient, the topographic factor, the wind directionality factor, the ground elevation factor and the square of the basic wind speed. The ground elevation factor is taken as unity and the directionality factor as the standard value for buildings. The exposure coefficient is tabulated against height for the assigned exposure category, with linear interpolation used to get the value at the mean roof height.

03

Topographic Factor

The topographic factor is formed from three coefficients that depend on the hill type, the ratio of the hill height to its horizontal length, the distance from the crest and the height above ground. For the assumed two-dimensional escarpment geometry these are read from the code tables, with linear interpolation on the height-to-length ratio. Because the third coefficient decays with height, the factor is largest at ground level and decreases up the wall.

04

Velocity Pressure Distribution and Simplification

The velocity pressure is tabulated level by level from ground to the mean roof height, combining the height-varying exposure and topographic factors. The note takes the maximum value, occurring at the mean roof height, and uses that single value throughout, while pointing out that the level-by-level values can be applied if greater accuracy is wanted. Working with one value simplifies the hand calculation and the subsequent load entry.

05

Two Internal Pressure Cases

The net wind pressure is the external pressure minus the internal pressure, and because the internal pressure coefficient can be positive or negative, every surface carries two possible values. The note therefore carries a positive internal pressure case and a negative internal pressure case through the whole calculation. Both must be represented in the model because different surfaces govern in each case.

06

External Pressure Coefficients

With the gust effect factor taken at the standard assumed value, and noting that it can instead be computed from the relevant code clause, wall pressure coefficients are selected for the windward, leeward and side walls from the plan aspect ratio, and roof coefficients are selected from the roof angle and the ratio of roof height to plan dimension. Each surface pressure is then the velocity pressure times the gust factor times its coefficient, evaluated for wind along each plan direction in turn.

07

Summary Table and Sign Convention

The results are collected into a table giving the net pressure on the windward, leeward and side walls and on the windward and leeward roof slopes, for wind along each plan direction, in each of the two internal pressure cases. A positive sign denotes pressure acting toward the inside of the building and a negative sign pressure acting outward. The magnitudes and signs differ markedly between the two cases, which is why both are needed.

08

Entering the Loads in midas Gen

Load cases are created for the full set of combinations, covering the two internal pressure cases, the two plan directions and the two pressure signs, with a separate case for the windward, leeward and side surfaces. The pressures are then entered as floor loads on the corresponding surfaces, with the sign corrected according to the direction in which the load actually acts on that face and a matching floor load type created for the opposite direction. Load combinations including the wind cases are generated as the final step.

정리

Wind loading on a gable hip roof building must be computed by hand under the ASCE 7-16 directional procedure, building the velocity pressure from the exposure, topographic, directionality and elevation factors and then applying wall and roof pressure coefficients for both positive and negative internal pressure. The resulting pressures are entered in midas Gen as floor loads on separate load cases for each internal pressure case, wind direction and sign, with careful attention to the sign convention, before load combinations are generated.

관련 자료

같은 카테고리와 주제에서 선별한 자료입니다.

STRUCTURE · MIDAS NOTE[EN_GEN] Input a wind load on the model with monoslope roof as per ASCE 7-16
STRUCTURE · MIDAS NOTE[EN_GEN] Input a wind load in the model with gable hip roof (two way) as per ASCE 7-16
STRUCTURE · TUTORIAL[EN_nGen] 21_Calculation of wind load as per ASCE 7-16
STRUCTURE · EXPERT COLUMN[KR_하영철.2016] 04_건축물에 작용하는 풍압력